Short-Circuit Withstand Tests of 2605SA1-based Amorphous Distribution Transformers - Archive ouverte HAL Accéder directement au contenu
Article Dans Une Revue IEEE Transactions on Magnetics Année : 2011

Short-Circuit Withstand Tests of 2605SA1-based Amorphous Distribution Transformers

Résumé

This paper deals with EDF Research and Development work for ERDF needs in terms of energy efficiency, focused on Amorphous Metal Distribution Transformers (AMDT). Many prototypes built on METGLAS® 2605SA1, rated 250 to 630 kVA from different manufacturers, were tested under short-circuit conditions according to IEC and ERDF standards. Some of the prototypes exceeded the accepted value of 4% of impedance variation after short-circuit. Rectangular windings offer poor resistance to short-circuit stresses. Small metal particles, detached from amorphous core, were found at the bottom of the tank. In that case, dielectric strength is not gifted. The results show the active part should be strong enough to support high electrodynamic forces produced during short-circuit test.
Fichier principal
Vignette du fichier
Article_final-SC.pdf (194.52 Ko) Télécharger le fichier
Origine : Fichiers éditeurs autorisés sur une archive ouverte
Loading...

Dates et versions

hal-00661849 , version 1 (20-01-2012)

Identifiants

Citer

Malick Mouhamad, Christophe Elleau, Frederic Mazaleyrat, Christian Guillaume, Bertrand Jarry. Short-Circuit Withstand Tests of 2605SA1-based Amorphous Distribution Transformers. IEEE Transactions on Magnetics, 2011, 47 (10), pp.14489-4492. ⟨10.1109/TMAG.2011.2155632⟩. ⟨hal-00661849⟩
215 Consultations
1218 Téléchargements

Altmetric

Partager