This paper presents a method for the sizing of a gapped-core nonlinear shunt reactor used for mitigation of overvoltages in a medium voltage distribution network with a high level of distributed generation. The study of the transient phenomena that occurs during reactor switching-in is also carried out. These phenomena include (i) inrush currents during switching due to saturation of the magnetic core, which is a silicon-steel (SiFe) iron core, and (ii) also the resulting voltage drop due to these high currents. The study shows the design a 1.4 Mvar shunt reactor with steps of 0.2 Mvar and presents inrush currents for the various steps.
Cet article présente une méthode pour le dimensionnement de selfs shunt non-linéaires avec entrefer utilisés pour limiter les surtensions dans un réseau de distribution de moyenne tension avec un niveau élevé de production décentralisée. L'étude des phénomènes transitoires qui se produisent pendant l'enclenchement du réacteur est également réalisée. Ces phénomènes comprennent (i) les courants d'appel pendant la commutation en raison de la saturation du noyau magnétique, qui est un noyau de fer-silicium (SiFe), et (ii) également la chute de tension qui en résulte en raison de ces courants élevés. L'étude montre la conception d'un réacteur shunt de 1,4 Mvar avec des gradins de 0,2 Mvar.