Analyse psychrométrique des systèmes de climatisation
Résumé
The air transformations are represented graphically on the psychrometric diagram, which is very non-linear. The sensible and latent heat may be decoupled, which allows the representation of air transformations by linear variations. The saturation curve may be also linearized in a point. If the mass flow rate and if the sensible and latent heat flows are known (i.e. if an analysis problem is treated), then, in steady-state, the coupled models of humid air transformations become a system of linear equations. This method is a computational alternative to the graphical solutions based on the moist air diagram which has the advantage to deal with a very large number of thermal zones.
Les transformations de l’air sont représentées graphiquement sur le diagramme psychrométrique qui est fortement non linéaire. Les chaleurs sensible et latente peuvent être découplées, ce qui permet de représenter les transformations par une variation linéaire, avec une erreur de moins de 3%. La courbe de saturation peut aussi être linéarisée autour d’un point. Si le débit massique d’air sec et si les flux de chaleur sensible et latente injectés dans les éléments des systèmes de climatisation sont connus (c. à d. si on traite un problème d’analyse), alors, en régime stationnaire, les modèles couplés des transformations de l’air humide deviennent un système d’équations linéaires. Cette méthode est une alternative informatique aux solutions graphique basées sur le diagramme de l’air humide qui offre l’avantage d’être applicables aux bâtiments avec un grand nombre de zones thermiques.
Domaines
Thermique [physics.class-ph]Origine | Fichiers produits par l'(les) auteur(s) |
---|